  • SO cord | Information by Electrical Professionals for Electrical . . .
    Does anyone know the max lenght SO or SJO cord I can use to connect equipment (such as beer canning and bottling equipment) The cord will hang from the j boxes with strain relief from the bar joists in a warehoue I have looked everywhere I can think of in the NEC for this, does anyone know
  • SO Cord Ampacity and Termination Temp per 110. 14 (C)
    With THHN etc and Type W portable cord, the NEC tables provide ampacities at various insulation temperatures, so they can be used to ensure compliance with 110 14(C), e g if you have 75C terminations you use the 75C column of the table Table 400 5(A)(1) for SO, SOW, SOO, SOOW etc cord
  • Type SOOW cord installed permanently outside
    Is type SOOW flexible cord allowed in permanent installations OUTSIDE a residence, that is to say, exposed to the weather? I have a 96 code book, and article 100 spells out clearly the differences between dry, damp, and wet locations It states that an outside location ie exposed to weather
  • Highbay Light Connection | Information by Electrical Professionals for . . .
    How would you connect a highbay LED light that only has a cord, no cord cap? If you put a junction box and insert the cord, would that be a mis-use of cord? Meaning the cord being a part of the permanent wiring Here's a link to the light
  • Cords and Receptacles above a Suspended ceiling
    The cord cannot be above the ceiling The receptacle can be mounted flush within the ceiling so that the cord is not above the ceiling but that's it You said access points, are these powered by 120 volt cord and plugs or are they powered with wall wart style transformers?
  • Use SO Cords | Information by Electrical Professionals for Electrical . . .
    Welcome to the forum Yes, SO cord can be used as a pendant from a busway in accordance with 368 56 (B) SO cord is listed as extra hard usage cord As for the quad box, 314 23 (H) (1) states "A box shall be supported from a multiconductor cord or cable in an approved manner that protects the conductors against strain, such as a strain relief connector threaded into a box with a hub A standard
  • Bus Drop Wiring | Information by Electrical Professionals for . . .
    I would never use so cord cord connectors with a rubber donut that marked strain relief on drops higher then 10' off the floor or heavy cable Several times I had to drop 30' of 6 4 cord and and used a Klems cable grip on a heavy spring attached to unistrut then a short loop of cable thru an approved non strain relief cord connector
  • SO Cord Drops to Machines?? | Information by Electrical Professionals . . .
    In my opinion that is not a pendant so which one of the following reasong would you say allows the use of cord for this? (2) Wiring of luminaires (3) Connection of portable luminaires, portable and mobile signs, or appliances (4) Elevator cables (5) Wiring of cranes and hoists (6) Connection of utilization equipment to facilitate frequent
  • SO or SJ cable in cable tray - Mike Holts Forum
    custmer wants cable tray with SO cord for power drops in equipment room also wants receptacle box attached to the tray Is any part of this OK? article 392 saye nothing about SO cable being permited in tray and nowhere anything about attaching J boxes or receptacle boxes to the cable tray
  • High bay lights | Information by Electrical Professionals for . . .
    Why do I need Cord and plug for my HIgh bay lights Why can’t I just run the so cord into the junction box Who says you need to be cord an plug?